22kv Dry Type Power Transformer (SCB)

Application: Power
Phase: Three
Core: Core-type Transformer
Cooling Method: Dry-type Transformer
Winding Type: Multi-winding Transformer
Certification: ISO9001-2000

Products Details

Basic Info.

Model NO.
SCB
Usage
Distribution Transformer
Frequency Characteristics
Power Frequency
Shape of Core
Ring
Brand
Rockwell
Transport Package
Wooden
Specification
IEC/ANSI/IEEE. BS
Trademark
Rockwell
Origin
China
HS Code
8504220000
Production Capacity
10000

Product Description

6kV up to 35kV Dry Type Transformer with Cast Epoxy Resin 
Dry Type Transformer Technical Data: 


22kv Dry Type Power Transformer (SCB)
Power-Cast transformers are available with specification as follows :

 
Rated Voltage HV coil : Up to 24kV  LVcoil : 0.48-4.16 KV
*Power-Cast transformers with multiple high voltage connections can also be supplied.
Tap Range Standard : ±2.5%, ±5%  Other ratings are available by arrangement.
Power Capacity Single phase : 20 - 2,000 KVA  Three phase : 50 - 10,000 KVA
Frequency : 50Hz, 60Hz   Typical % impedance voltage : 4-8%.
Connections HV coil : Delta  LVcoil : Wye with neutral point
* Other connections are available to meet requirements.
Temperature Ratings HV coil : Class F LVcoil : Class F
Max. ambient temperature : 450 C   Temperature rise limitation : 1800 C
 

1. Rated capacity : 30~16000kVA

2. Rated HV : 6kV to 35 kV

3. Frequency : 50Hz or 60Hz

4. Cooling methods : ONAN or ONAF

5. Tapping Range : ±5%   ±2x2.5%   ±4x2.5%

6. Regulator way : off-circuit-tap-changing or on-load-tap-changing

7. Phase : Single Phase or Three Phases

8. Connection Symbol : Yyn0 or Dyn11 or others

9. The altitude of installation could not be over 1000m;environment temperature should be less than 40

10. Coil temperature rise : 1000K

11. Cooling methods : AN or AF

12. Crust prevention class : IP00, IP20, IP23

13. Insulation class : F class

14. Insulation level:

     10KV,power frequency withstand voltage 35KV,thunder impact voltage 75KV

     20KV,power frequency withstand voltage 50KV,thunder impact voltage 125KV

     35KV,power frequency withstand voltage 70KV,thunder impact voltage 170KV

15. Product Standard : GB1094    GB6450     GB/T10228     DIN42523        IEC726

16. Can run in 100% relative humidity or other harsh environment.
 