Basic Info.
Model NO.
LXK
Insulating Medium
Epoxy Resin
Installation
Busbar Type
Magnetic Circuit Structure
Single Stage Type
Voltage Transformation Principle
Electromagnetic Type
Transport Package
Export Box
Trademark
DGG
Origin
China
HS Code
8504311000
Production Capacity
100000PCS/Year
Product Description
GENERAL
These series of transformers are used indoors. They are used for three phases of overdriven current protection in the electric not-useful-ground neutral system up to rated frequency 50Hz or 60Hz and rated voltage 35kV. The transformers are fitting with the relay too.
Being installed, at first, make the product dimidiation. Then make it coalition use bolt. Can be loaded in hot-line conditions.
MODEL AND MEANING
NORMAL ENVIRONMENTAL CONDITIONS
TECHNICAL PARAMETERS
OUTLINE AND INSTALLATION DIMENSIONS
These series of transformers are used indoors. They are used for three phases of overdriven current protection in the electric not-useful-ground neutral system up to rated frequency 50Hz or 60Hz and rated voltage 35kV. The transformers are fitting with the relay too.
Being installed, at first, make the product dimidiation. Then make it coalition use bolt. Can be loaded in hot-line conditions.
MODEL AND MEANING
NORMAL ENVIRONMENTAL CONDITIONS
- Altitude: Should not exceed 1000m
- Ambient temperature: -5ºC ~ +40ºC
- Air relative humidity: ≤85%
- Air relative site: Indoor.
TECHNICAL PARAMETERS
- Rated secondary current: 5A or 1A
- Power factor: cosφ=0.8(lag)
- Rated frequency: 50Hz or 60Hz
- Rated primary current, rated output, and accurate level see table 1
- Insulating property: primary winding to secondary winding and ground, and secondary winding to the ground can bear the power frequency withstand voltage 3kV for 1min.
Rated primary current(A) | Accuracy Class | Rated Output (VA) |
60-75 | 10P5 | 2.5 |
100 | 3.75 | |
150 | 2.5 | |
200-300 | 3.75 | |
400-600 | 5 | |
100 | 2.5 | |
150-200 | 10P10 | 2.5 |
300-400 | 3.75 | |
500 | 5 | |
600 | 5 |
Type of Relay | Connecting Method of Relay Windings | Relay Calibration | Primary Zero Sequence Current |
LJK-Φ120 LJK-Φ160 | Series | 15x1 | 2-5 |
30x1 | |||
Parallel | 15x2 | 3-8 | |
30x2 | |||
LJK-Φ200 | Series | 15x1 | 3-6 |
30x1 | |||
Parallel | 15x2 | 3-10 | |
30x2 |
OUTLINE AND INSTALLATION DIMENSIONS
Model Number | ΦD | Φd | H | h | a | b | c | e |
LXK(KXLXK) - Φ80 | 165 | 80 | 175 | 82.5 | 120 | 104 | 120 | 56 |
LXK(KXLXK) - Φ100 | 180 | 100 | 195 | 92.5 | ||||
LXK(KXLXK) - Φ120 | 204 | 120 | 215 | 102.5 | ||||
LXK(KXLXK) - Φ150 | 234 | 150 | 245 | 117.5 | ||||
LXK(KXLXK) - Φ180 | 263 | 180 | 275 | 132.5 | ||||
LXK(KXLXK) - Φ200 | 303 | 200 | 320 | 156 | ||||
LXK(KXLXK) - Φ240 | 347 | 240 | 385 | 185 | 160 | 120 | 142 | 80 |